Under-voltage/over-voltage relays,RMV-112D

Maker: DEIF

Model: RMV-112D

 

Name- Under-voltage/over-voltage relays

Maker: DEIF

Model: RMV-112D

Technical Specification:
Meas. range
(Un) 57.7-63.5-100-110-127-200-220-230-240-380-400-415-440-450-480-660-690 V
AC
UL/cUL Listed: 57.7 to 450 V AC
Frequency range :
40 to 45 to 65 to 70 Hz
Max. input voltage
1.2 × Un, continuously
2 x Un for 10 s
Load
2 kΩ/V
Outputs
RMV-112D 1 minimum 1 maximum contact
Contact type
Relays B C: Normally energised (“NE”), or normally de-energised (“ND”) with
or without latch circuit (“L”)
Relay contacts
1 change-over switch per relay
Contact ratings
250 V AC/24 V DC, 8 A (200 x 103 change-overs at resistive load)
UL/cUL Listed: Resistive load only
Contact voltage
Max. 250 V AC/150 V DC
Response time
<100 ms
Temperature
-25 to 70 °C (-13 to 158 °F) (operating)
UL/cUL Listed:
Max. surrounding air temp. 60 °C/140 °F
Temperature
drift Set points: Max. 0.2 % of full scale per 10 °C/50 °F
Galv. separation
Between inputs and outputs: 3250 V – 50 Hz – 1 min.
Supply voltage (Un)
57.7-63.5-100-110-127-220-230-240-380-400-415-440-450-480-660-690 V AC
±20 % (max. 3.5 VA)
24-48-110-220 V DC -25/ 30 % (max. 2 W)
UL/cUL Listed: Only 24 V DC and 110 V AC
DC supply must be from a class 2 power source
Climate
HSE, to DIN 40040
EMC
To IEC/EN 61000-6-1/2/3/4
Connections Max.
4.0 mm2 (single-stranded)
Max. 2.5 mm2 (multi-stranded)
Materials
All plastic parts are self-extinguishing to UL94 (V1)
Protection Case:
IP40. Terminals: IP20, to IEC 529 and EN 60529
Type approval
The Uni-line components are approved by the major classification societies. For
current approvals see www.deif.com or contact DEIF A/S.
UL markings
UL Listed only on request
UL Listing will be lost if the product is re-customised outside DEIF DK’s production plant
Wiring: Use 60/75 °C (140/167 °F) copper conductors only
Wire size: AWG 12-16 or equivalent
Installation: To be installed in accordance with the NEC (US) or the CEC (Canada)

Category: