Name- Phase Failure with under voltage/over voltage relay
Manufacturer : Minilec Group
TYPE : ALV D2
Technical Specifications :
Supply Voltage
System : 110 / 240 / 380 / 415 / 440 V AC ±20% 50 / 60 Hz
Auxillary : 110 V (Fixed) or (220 – 230 – 240) or (380 – 415 – 440) V AC ±20% selectable
Output Contacts
Output Contacts2 CO
Trip Setting (Volts)
Phase Sequence Yes
Phase Unbalance 40 V ±6 V (fixed)
Under Voltage For 380-440V AC
For 220-240V AC
For 110 V AC 80% to 95% (adjustable) of auxillary supply (±2% of set value)
Under Voltage For 380-440V AC
For 220-240V ACFor 110 V AC105% to 120% (adjustable) of auxillary supply (±2% of set value)
Trip Time Delay
On Phase Failure3.5 secs. ± 1.5 sec
On UV/OVLess than 2 secs.
Resetting Mode
Resetting Mode : Auto Reset
Weight : Weight400 gms.
Dimensions (mm)
Overall (L x W x D)76 x 56.5 x 117.5
Mounting (L x W)67 x 46 alt / 35 mm rail Mounting
Note:
Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)
* CE marked products available on request.